3.4 Operation Processes
3.4.1 Normal Mode Start-up
Warning!
Please don’t close the battery line switch/fuses before start-up the
rectifier of UPS if the UPS don’t install optional DC Cold Start Kit.
(1) Close UPS Mains Input and Bypass Input Switches.
(2) Select →Command→Operation→Normal mode on LCD display.
(3) Return to Mimic Display. Wait for few minutes, the rectifier will be started.