SECTION 2 – SPECIFICATIONS
+/- 5% of reading or 5 CFM, whichever is greater
< 1 second control signal response (full stroke cycle time based on actuator type)
Standard: < 1.5% FS at max operating pressure
"S" Option: < 0.5% FS round valves, < 1% FS rectangular valves @ max operating pressure
3”wc Differential Pressure Across Valve
Open, Closed or Last Position (based on actuator type selection)
Airstream: -20 to 165 deg. F for all Standard Valve Models
-20 to 375 deg. F for the High Temp SS Valve Models
Ambient: -20 to 125 deg. F Storage: -40 to 165 deg. F
24VAC +/- 20% 50-60Hz or 24 VDC +/- 10%
Max Power for Valve Size 06-24: 28VA or 16W for units with actuator type 3 & 5
11VA or 7W for units with actuator type 7
Max Power for Valve Size 36, 48: 51VA or 29W for units with actuator type 3 & 5
17VA or 11W for units with actuator type 7
If monitor FHM1 is connected to AVC, increase above values by 3VA or 1W
If monitor FHM3 is connected to AVC, increase above values by 6VA or 3W
AI-1; Software Configurable for Voltage or Current, 12-bit resolution
Voltage: 0-10Vdc Range, 1M ohm Impedance
Current: 0-20mA Range, 500 ohm Impedance
AI-2, AI-3; Software Configurable for Resistance range of 20K ohm or 100K ohm
500uA Current Source for 20K ohm Range, 100uA Current Source for 100K ohm Range
DI-1 and DI-2; Dry-contact inputs
AO-1 and AO-2; Software Configurable; 0-20mA, 4-20mA, 0-10v, 2-10v, 0-5v or 1-5v
12-bit Resolution, capable of driving 1K ohm load
SPST, NC/NO contacts, rated load 1A @ 30 vDC or 0.3A @ 125vac
Max operating voltage = 125VAC or 60 vDC
Max carry current = 1A, Max switching capacity = 37 VA, 30W
EIA 485 2-wire BACnet MS/TP
Full Master Node State Machine
Data Rates 9600, 19200, 38400, 76800 and 115200
Mac address is software configurable
¼ Unit Load Receiver Input Impedance, bias & EOL termination not provided within the AVC
USB 2.0, Isolated, Type C Connector, Optional Bluetooth (Ver 4.2 or later)
LED Indicators for Power, Alarm, AO, BACnet, USB, AVC Status, Bluetooth & AccuNet
2 and 3 position vertical pluggable screw terminal blocks
EMC Directive 2004/108/EC
Low Voltage Directive 2004/108/EEC