22
ActronConnect Installation & Commissioning Guide - Website
Doc. No.9590-1001 Version No.3.0 150901C
WIRING DIAGRAM
R
This drawing remains the intellectual property of Actron Engineering
Pty Ltd. Reproduction, modification and/or distribution are prohibited
without written consent.
Revision
Description:
Drawing No:
A
WD2004
Rev.
Description
Date
By
PCR
ORIGINAL
A4
Size:
Base
Model No:
Variation:
Variation Code:
A
ERM EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY
LEGEND
AMIB
ACM
EXV
IF
IFRC
TX
WC
EMC
F
8Z-VAV
05-11-2013MH
Drawn:
Date:
Approved:
MJH
Date:
05-11-2013
NEUT
NEUT
LINE 1
ACT
CB-1
10 A
FIELD WIRING BY
INSTALLER
SCRN
COM
PWR
KEY
COM
DATA
EARTH
NEUT
ACT
INDOOR
COIL IN
SENSOR
OUTDOOR
IF-1
1 EC
EC CONTROL
ECM
CONTROL
MODULE
INDOOR FAN (IF)
INTERNAL AUTO RESET
OVERLOAD PROTECTION
FERRITE
EMC-1
E
N
A
N
A
PCB JUMPER PIN
POSITION TABLES
Jumper Pin
Position
A/C Model
D
PCB Model: AMIB-PVVM
C
B
A
E
ERM3-17AS
ERM4-19AS
N/A
N/A
ERM2-14AS
(+) A B (-)
POWER
COM
KEY
SENSOR
POWER
COM
KEY
SENSOR
DO NOT
CONNECT
SCREEN
AND SENSOR
AT WALL
CONTROL
SEE JUMPER PIN POSITION
TABLES FOR CORRECT SETTING
ULTIMA MODULE
(8Z-VAV)
AMIB
DATA
ZONE
8
ZONE
7
ZONE
6
ZONE
5
ZONE
4
ZONE
3
ZONE
2
ZONE
1
TO ZONE 2 - 8
240V
MAINS
ZONE
MOTOR
ZONE
CONTROL 1
ZONE
SENSOR 1
LOG
RJ45 SOCKETS FOR ACTRON AIR
CAT5E SPEC CABLES ONLY
FIELD WIRING
FERRITE
(IF FITTED)
SCREEN
WIRES
DATA CABLE SCREEN WIRE -
KEEP AS SHORT AS POSSIBLE
MAINTAIN TWISTED PAIR
UNTIL TERMINAL ON AMIB
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO THE SCREEN TERMINAL ON INDOOR UNIT
& SCREEN FOIL CLAMPED TO P-CLIP ON OUTDOOR UNIT
+V
-V
N
A
AC IN
DC OUT
ADJ
ACM POWER SUPPLY
(240VAC - 12VDC 1.3A)
BROWN
BLUE
GREEN / YELLOW
BRN / WHITE (GREEN)
BROWN
IMPORTANT:
DO NOT MOUNT WIFI MODULE
DIRECTLY ON EVAPORATOR UNIT
- FOR OPTIMUM PERFORMANCE OF
WIFI SIGNAL MOUNT 1 METRE AWAY
& NOT ABOVE EVAPORATOR
- MOUNT MINIMUM 1 METRE BELOW
ROOF
WIFI
MODULE
3G
LPW W IFI E TH
E2
RST
MODE
ETH AC
PWR
P1
ANTENNA
BROWN
BLUE
BROWN
BLUE
DATA
IMPORTANT :
DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
- FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL
MOUNT 1 METRE AWAY (OR GREATER) AND
NOT ABOVE THE INDOOR UNIT.
- MOUNT MINIMUM 0.5 METRE BELOW ROOF LINE.