MCBA PArAMeters for the sPeCiAlist
660Y1400 - A
SETTING THE PARAMETER: only accessible using the code
Factory settings Factory settings
STEP Display Parameter Description HM 25 TC HM 35 TC HM 45 TC HM 70 TC HM 85 TC HM 120 TC HM 71 HM 101 HM 201
p. 1 9
Booster 00 = OFF [minute].
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
p. 2 0
Night time central heating reduction °C.
. 1 0 . 1 0 . 1 0 . 1 0 . 1 0 . 1 0 . 1 0 . 1 0 . 1 0
p. 2 1
Increase of the primary temperature set point to
generate hot water..
. 20 . 20 . 20 . 1 0 . 1 0 . 1 0 . 05 . 05 . 05
p. 22
Max. fan speed in heating
mode [rpm. X 100.
Natural gas
. 44 . 63 . 68 . 49 . 60 . 53 . 46 . 60 . 52
Propane
. 4 1 . 65 . 69 . 45 . 55 . 53 . 42 . 54 . 47
p. 2 3
Max. fan speed in central
heating mode [rpm.].
Natural gas
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
Propane
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
p. 2 4
Max fan speed in domestic hot
water mode
[rpm X 100.
Natural gas
. 44 . 63 . 68 . 49 . 65 . 53 . 46 . 60 . 59
Propane
. 4 1 . 63 . 69 . 45 . 60 . 53 . 42 . 54 . 53
p. 2 5
Min. fan speed in DHW mode
[rpm].
Natural gas
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
Propane
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
p. 2 6
Min fan speed in domestic hot
water mode
[rpm X 100.
Natural gas
. 20 . 20 . 20 . 1 9 . 1 9 . 1 3 . 1 4 . 1 5 . 1 5
Propane
. 24 . 24 . 24 . 1 9 . 1 9 . 1 3 . 1 4 . 1 5 . 1 5
p. 2 7
Min fan speed
[rpm X 100.
Natural gas
. 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00 . 00
Propane