ENMCBA PArAMeters for the sPeCiAlist
660Y1400 - A
SETTING THE PARAMETERS
Only accessible using the code
Factory settings
STEP Display Parameter Description HM 25 / 35 / 45 / 70 / 85 / 120 TC HM 71 / 101 / 201
p. 1 0
Minimum central heating temperature using outdoor sensor..
. 60 . 60
p. 1 1
Minimum outdoor temperature [adjustment of the heating curve].
.-10 . 00
p. 1 2
Maximum outdoor temperature [adjustment of the heating curve].
. 18 . 20
p. 1 3
Frost protection temperature.
. 0 1 . 05
p. 1 4
Correction for outside temperature.
. 00 . 00
p. 1 5
Maximum flow temperature of the 2
nd
circuit.
. 50 . 60
p. 1 6
Minimum flow temperature of the 2
nd
circuit.
. 20 . 30
p. 1 7
Hystérésis of the 2
nd
circuit temperature.
. 03 . 0 1
p. 1 8
T lock: 00 = DISABLED
Locks the heat demand, if the heating set-point T° is lower than the
parameter value..
. 00 . 00