EN
en
28
MCBA PArAMeters for the sPeCiAlist
660Y1400 - A
Factory settings
STEP Display Parameter Description HM 25 TC HM 35 TC HM 45 TC HM 70 TC HM 85 TC HM 120 TC HM 71 HM 101 HM 201
p. 8 4
Max. T6 temperature limit
. C°
. 80 . 80 . 80 . 80 . 80 . 80 . 80 . 80 . 80
p. 87
Maximum dT1/
dt [x 0.1 °C/sec.]
. 30 . 30 . 30 . 30 . 30 . 30 . 30 . 30 . 30
p. 89
Maximum dT3/
dt [x 0.1 °C/sec.]
. 20 . 20 . 20 . 20 . 20 . 20 . 20 . 20 . 20
p. 90
Dierence T1 - T2 for modulation
. 10 . 10 . 10 . 10 . 10 . 10 . 15 . 15 . 15
p. 96
Pulses per rotation/PWM frequen-
cy
. 92 . 92 . 92 . 92 . 92 . 92 . 92 . 92 . 93
p. 97
External ignition/start attempts
. 05 . 05 . 05 . 05 . 05 . 05 . 05 . 05 . 05
p. 100
Maximum NTC1-NTC2 time [sec.
X 15]
. 40 . 40 . 40 . 40 . 40 . 40 . 40 . 40 . 40
p. 101
Minimum to maximum time in CH
mode [sec.]
. 60 . 60 . 60 . 60 . 60 . 60 . 60 . 60 . 60
p. 105
System 1 options
.-120 .-120 .-120 .-120 .-120 . 08 . -128 . -128 . -128
p. 106
System 2 options
. 108 . 108 . 108 . 108 . 108 . 108 . 116 . 116 . 116
p. 109
Protection options 2
. 32 . 32 . 32 . 32 . 32 . 32 . 32 . 32 . 32
p. 113
Additional parameter 0
[Value + 256]
. 119 . 119 . 119 . 119 . 119 . 247 . 127 . 127 . 127