VII. Troubleshooting
The Advantage MegaTron controller is designed for many years of trouble free
operation. Should a problem occur, refer to the following chart to help identify the
problem. If replacement is required, follow the procedures listed in the Warranty and
Factory Service portion of this manual.
SYMPTOM POSSIBLE CAUSE SOLUTION
False reading ..................... Bad or dirty electrode Clean, as needed
Out of calibration Calibrate unit
Will not calibrate................. Dirty electrode Clean electrode
Faulty electrode Replace electrode if needed
Faulty wiring to electrode Replace electrode if needed
No system power…………..Check power source Plug into different receptacle
Check fuse Replace as needed
Check connections Make sure ribbon cables are secure
Pulse timer not activating... Check wiring Repair as needed
Check external device Repair/replace as needed
Outputs not energized........ No flow Check sample line for
clogged pipes or strainers
Check fuse Replace as needed
22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantage Controls MegaTron Series and is the answer not in the manual?

Advantage Controls MegaTron Series Specifications

General IconGeneral
BrandAdvantage Controls
ModelMegaTron Series
CategoryController
LanguageEnglish

Related product manuals