ADAM-6200 User Manual 164
$aaCjCh
Name Clear Latch Alarm
Description Sets the High/Low alarm to OFF (no alarm) for the specified input
channel in the addressed ADAM-6200 module
Syntax $aaCjCh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave net-
work address of an ADAM-6200 module. (Always 01)
Cj identifies the desired channel j (j : 0 to 7).
Ch is the Clear Latch Alarm command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)
Response !aa(cr) if the command was valid
?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave address of the corre-
sponding ADAM-6200 module.
(cr) represents terminating character, carriage return (0Dh)
Example Command: $01C1CL(cr)
Response: !01(cr) Channel 1 of the ADAM-6200 module at address
01h is instructed to set its Low alarm state to OFF. The system con-
firms it has done so accordingly.

Table of Contents

Other manuals for Advantech ADAM-6251

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-6251 and is the answer not in the manual?

Advantech ADAM-6251 Specifications

General IconGeneral
BrandAdvantech
ModelADAM-6251
CategoryControl Unit
LanguageEnglish

Related product manuals