3
 
 
Notes: 
1.  Consult the National Electric Code for proper sizing for wire lengths over 24 ft. 
2.  When sizing the generator, the total power usage of your recreational vehicle must be 
considered. Keep in mind generators lose power at high altitudes and from lack of 
maintenance. 
3.  CIRCUIT PROTECTION: Time Delay Fuse or HACR Circuit Breakers Required.
 
INSTALLATION INSTRUCTIONS
 
1. PRECAUTIONS 
A.  Read installation and operating instructions carefully before attempting to start your 
air conditioner installation.   
B.  The manufacturer will not be liable for any damages or injury incurred due to failure to 
follow these instructions. 
C.  Installation must comply with the National Electrical Code and any State or Local 
Codes or regulations. 
D.  DO NOT add any devices or accessories to this air conditioner except those 
specifically authorized by manufacturer. 
E.  This equipment must be serviced by qualified personnel and some states require 
licensed personnel. 
 
2. CHOOSING A LOCATION FOR THE AIR CONDITIONER 
 
This product is designed for use as a RV roof top air conditioner. The use of this product in 
other applications will void the manufactures warranty. 
 
A. NORMAL LOCATIONS: 
  The air conditioner is designed to fit over an existing roof vent opening. When the vent is 
removed, it normally creates a 14-1/4" x 14-1/4" ±1/8” opening. 
 
B. OTHER LOCATIONS: 
  When a roof vent is not available or another location is desired, the following is recommended: