Surge Meet IEEE 587 standard
Operation
Elevation: 6,000m max, Humidity: 0%-95%(without
condensation formation), Temperature:
0-40 deg C
Audible noise
<40dBA (1 meter from
surface)
<45dBA (1 meter from surface)
ENVIRONME
NT
Storage
condition
15000 meters max. elevation
APPENDIX B.2 SPECIFICATION
MODEL 2500VA 3000VA 1000AL 2000AL 3000AL
Capacity 2500VA 3000VA 1000VA 2000VA 3000VA
Voltage 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single phase
INPUT
Frequency 50 or 60Hz +/-5% (auto sensing)
Voltage
(on
battery)
Pure sine wave output at nominal +/-5%
Frequency
(on
battery)
50 or 60Hz +/-0.5%
OUTPUT
Voltage
Regulation
AVR
AVR automatically increase output voltage 15% above input
voltage if -9% to-25% of nominal. AVR decrease output voltage
15% below input voltage if+9% to +25% of nominal
Spike
Protection
320 Joules, 2ms
Unit Input Breaker for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz
Overload
Protection
UPS automatic shutdown if overload exceeds 110% of nominal
at
20 second and 125% at 2 seconds.
Transfer Time 2~4 milliseconds, including detection time
PROTECTION
AND
FILTERING
Short Circuit UPS output cut off immediately or input fuse protection
Type Hot swappable, Sealed, Maintenance-free lead acid
Typical Battery
Life
3 to 6 years, depending on number of discharge cycles and
ambient temperature
Typical
Recharge Time
4 hours (to 90% of full capacity)
Nominal Battery
Voltage
48V 48V 24V 48V 48V
Charge Current 2A 2A 4A 4A 4A
BATTERY
Supplied
Battery Packs
Built-in
External
Pack
Upon
request
Upon
request
Upon
request