Recommended output circuit breaker current specifications:
UPS power rating Output mode Breaker current
10000VA
1 phase output 63A
3 phase output 32A
15000VA
1 phase output 100A
3 phase output 50A
20000VA
1 phase output 125A
3 phase output 63A
Recommended battery circuit breaker current specifications:
UPS power rating Breaker current
10000VA 80A
15000VA 63A
20000VA 80A