EasyManua.ls Logo

AEG PROTECT C. 10000 - Page 12

AEG PROTECT C. 10000
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Overload behaviour up to 105 % continuous;
in battery mode > 105 % for 10 s
Short circuit behaviour 3 x I
N
for 300 ms
Battery
Autonomy time (full load with internal battery)
PROTECT C. 6000 8 min.
PROTECT C. 10000 5 min.
Autonomy times with external optional battery expansions
(only for PROTECT C. models):
Autonomy times (full load)
Coupled
battery modules
C.6000 C. 10000
1
25 min. 15 min.
2
45 min. 25 min.
3
60 min. 33 min.
Rated direct voltage (intermediate circuit)
PROTECT C. 6000 (S) 240 Vdc
PROTECT C.
10000 (S) 240 Vdc
Battery charging current
PROTECT C. 6000 2.0 A
PROTECT C. 6000 S 4.2 A
PROTECT C.
10000 2.0 A
PROTECT C.
10000 S 4.2 A
Recharge time ~ 7 h (UPS with internal
to 90% of rated capacity battery only)
(PROTECT C. – models) ~ 11
h (with 1 battery
expansion)
~ 16 h (with 2 battery
expansions)
~ 24 h (with 3 battery
expansions)

Table of Contents