42
Description Adjustable parameters Presetting
Control
commands
from serial port
[enabled], [disabled]
If enabled, control commands are
accepted through Serial, USB port
and cards in the communication slot,
else control is restricted to the LCD
panel of the UPS.
enabled
Output
voltage
[200V], [208V], [220V], [230V],
[240V], [auto-sensing]
Setting only available in
UPS stand-by mode.
auto-sensing
Output
frequency
[50Hz], [60Hz], [auto-sensing]
Setting only available in
UPS stand-by mode.
auto-sensing
Load alarm
level
(Overload)
[10%], [20%], [30%], ... [100%]
NOTE: The level can be set in 10%
increments so a possible overload is
detected early.
100%
Power strategy [High performance mode (normal)],
[Economical mode (ECO)],
[Converter mode]
Setting only available in
UPS stand-by mode.
normal
Start w/o mains [enabled] [disabled]
cold Start
enabled
Site wiring
fault alarm
[enabled], [disabled]
disabled