Gener
al Data
Classification VFI SS 211 to IEC 62040–3
Double conversion technology
Overall efficiency (full load)
PROTECT C. 1000 R (S) 85 %
PROTECT C. 2000 R (S) 85 %
PROTECT C. 3000 R (S) 88 %
PROTECT C. 6000 R > 88 %
Noise level (1m distance)
PROTECT C. 1000 R (S) < 45 dB (A)
PROTECT C. 2000 R (S) < 50 dB (A)
PROTECT C. 3000 R (S) < 50 dB (A)
PROTECT C. 6000 R < 55 dB (A)
Type of cooling Forced cooling
by variable speed fans
Operating temperature range 0°C to +40°C
Recommendation +15°C to
+25°C (due to battery
system)
Storage temperature range 0°C to +40°C
Relative humidity < 95%, non-condensing
Max. site altitude up to 1000 m at full load
If the UPS is installed or used
in a place where the altitude
is above than 1000m, the
output:
Altitude (m) 1000 1500 2000 2500 3000
Derating
Power
100% 95% 90% 85% 80%
19