7 Maintenance
The PROTECT C.R consists of advanced and resistant
components. To guarantee a continuous and high availability
it is recommended to check the unit (especially the batteries
and the fans) in regular intervals (at least every 6 months).
CAUTION:
Follow safety and security regulations
unconditionally!
7.1 Charging the Battery
The battery is automatically charged when the mains is
present, irrespective of the operating mode.
The complete charging time of the battery after a length
discharge period depends, above all, on the number of
additional external battery units.
Charging time up to 90% of rated capacity
Coupled
battery modules
C. 1000 R C. 2000 R C. 3000 R C. 6000 R
Integr. battery 5 h - - -
1 24 h 5 h 5 h 5 h
2 40 h 14 h 14 h 14 h
3 - 24 h 24 h 24 h
4 - 32 h 32 h 32 h
5 - 40 h 40 h 40 h
7.2 Maintenance
The following maintenance work should be performed:
Task Interval Described in
Visual check 6 months Chapter 7.2.1
Battery / fan check 6 months Chapters 7.2.2 / 7.2.3
42