5.2 External Battery Expansions
PROTECT C. 2000 R, C. 3000 R and C. 6000 R require at least
one external battery module for accurate operation. To achieve
longer backup time, it is possible to connect multi-battery
packs. Connect exclusively
the following products together:
PROTECT C. 1000 R with PROTECT C. 1000 R BP
PROTECT C. 2000 R with PROTECT C. 2030 R BP
PROTECT C. 3000 R with PROTECT C. 2030 R BP
PROTECT C. 6000 R with PROTECT C. 6000 R BP
PROTECT C.R with 1 battery expansion
Fig.: PROTECT C. 2000 R and C. 2030 R BP
1. Check the correct fit of the UPS and the battery
unit (compare the stated DC voltage on the label
of the UPS and the battery unit).
Never connect different battery voltage levels
with each other!
2. Now connect both battery connectors using the
supplied battery connection cable. When
connecting, make sure that you push the plug
quickly and firmly in the battery connectors.
28