TROUBLESHOOTING
8-11
5. The blower proof switch should show
continuity while the blower is running.
6. If the blower proof switch does not show
continuity, remove the switch and check for
signs of blockage. If there is blockage, clean
the switch and retest.
7. If the blower proof switch shows continuity,
disconnect AC power to the unit.
8. Disconnect the 1 ¾" connector from the
control panel.
9. Referring to system schematic 161453 in
Appendix H, locate wires #154 and #155
and check both for continuity.
10. Check the switch end of wires #154 and
#155 for loose connections.
11. Check the connector end for worn pins
and/or proper pin insertion.
12. If continuity, the connector and pins are
okay, reconnect wires #154 and #155 to the
blower proof switch.
13. Reconnect the 1 ¾" connector to the control
panel.
14. Reconnect AC power to the unit and start
the unit.
15. If the SYSTEM FAULT LOW AIR
PRESSURE fault still persists, replace the
control panel.
8.7.4 PURGE INTERLOCKS
If the SSOV proof of closure switch or the
air/fuel valve open position switches fail to prove
closed during the start up sequence, the unit will
shut down and the Annunciator will display the
message SYSTEM FAULT, PURGE
INTERLOCKS. To determine the cause of the
fault perform the following:
1. Remove the air/fuel valve cover.
2. Clear the Annunciator and start the unit.
3. If the Annunciator displays the message
PURGE INTLK OPEN and the air/fuel valve
does not rotate, proceed to section 8.6.7.
4. If the air/fuel valve rotates to its full open
position and engages the air/fuel valve open
proving switch, and the Annunciator still
displays SYSTEM FAULT, PURGE
INTERLOCKS, proceed to section 8.6.6.
8.7.5 SSOV PROOF OF CLOSURE SWITCH
1. Disconnect AC power to the unit.
2. Loosen the two setscrews securing the
safety shut-off valve actuator to the safety
shut-off valve body.
3. Rotate the actuator portion clockwise
exposing the electrical cover plate and
tighten the two previously loosened
setscrews.
4. Remove the electrical cover plate exposing
the control wiring
5. Referring to the system schematic 161453 in
Appendix H, remove wires #148 and #149
from the proof of closure switch.
6. Connect an ohmmeter across the NC,
normally closed, and the C, common,
terminals.
7. The switch should show continuity. If it does
show continuity proceed to step 16.
8. If the switch does not show continuity,
remove the actuator from the valve body.
9. Looking at the actuator from the bottom,
push on the lever closest to the bottom of
the actuator.
10. Observe the ohmmeter while pushing on the
lever. Pushing downward on the lever
should make continuity. Releasing the lever
should break continuity.
.
11. If continuity makes and breaks, slightly bend
the arm toward the bottom of the actuator.
12. Reset the actuator onto the valve body while
observing the ohmmeter.
13. If continuity is now okay, reconnect wires
#148 and #149, replace the electrical cover
plate and reassemble the actuator to the
valve body.
14. If there is no continuity, replace the actuator
or switch.
15. Start the unit. If the unit sequence resumes
normal operation, proceed no further. If the
Lockout still persists, proceed to Step 16.
16. Disconnect AC power and remove wires
#148 and #149 from the proof of closure
switch. Disconnect the 1" connector from the
control panel.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco Benchmark Series and is the answer not in the manual?

Aerco Benchmark Series Specifications

General IconGeneral
ModelBenchmark Series
CategoryBoiler
ManufacturerAerco
Vent MaterialStainless Steel
Fuel TypeNatural Gas
Operating Pressure160 psig
Control SystemAerco Control System
Heat Exchanger MaterialStainless Steel

Related product manuals