EasyManua.ls Logo

Aerco Modulex MLX Series - Boiler Freeze Protection

Aerco Modulex MLX Series
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MC2: 10/03/12 Page 17 of 90
AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288
GF-115-H
OMM-0083_0B
Modulex MLX Series Gas Fired Boiler System
Operation and Maintenance Manual
Chap 2: General
Description
2.7 Boiler Freeze Protection
Should the boiler water outlet temperature decrease to less than 44.6°F (7°C), the system pump will start.
Should temperature decrease to less than 37.4°F (3°C), all heat modules will start at minimum output until
the return temperature reaches 50°F (10°C). Such a protection device is exclusively for the boiler. For the
protection of the whole system, a second freeze protection thermostat is necessary to switch on the
heating system pump.
NOTE
If glycol is used as antifreeze in the boiler, a back flow preventer must be
installed in the make-up/fill line.

Table of Contents

Other manuals for Aerco Modulex MLX Series

Related product manuals