22
FWR 1406 - 5388000_02
Power supply = 230V ~ 50Hz.
TECHNICAL DATA
Mod. FW 130R 160R
Cooling capacity W (max.) 2900 4000
Energy Eciency Class A A
EER 4.08 4.65
Humidity removed l/h 1.78 1.78
Input power W 710 860
Input current A 3.55 4.02
Heang capacity with water coil (BVR1) W 4350 5200
Water ow rate (BVR1) l/h 600 600
Pressure drops (BVR1) kPa 12,6 12,6
Heang capacity electric coil (BR26) W 1200 1200
Fans n. 2 2
Air ow rate
m
3
/h (max.) 470 690
m
3
/h (med.) 390 525
m
3
/h (min.) 270 375
Fans speed
g/m (max.) 800 1140
g/m (med.) 660 885
g/m (min.) 500 665
Sound pressure dB (A) 44 47,5
Water consumpon at 30-35°C l/h 586 804
Condenser pressure drops kPa 22 40
Refrigerant charge R410A g 750 830
Input nominal power consumpon * W 1120 1500
Nominal imput current * A 4.97 6.65
Input current A 18 32
Water connecons ø 1/2”F 1/2”F
Level of sound pressure (A-weighted) measured in an 85 m
3
semi-reverberant test chamber with reverberation time Tr = 0.5s.
* In accordance with UNI EN-60335
Data declared in accordance with EN-14511
Cooling :
- Room air temperature 27°C B.S. ; 19°C B.U.
- Entering water temperature 30°C
- Leaving water temperature 35°C
- Max speed
Heating (BVR1) :
- Room air temperature 20°C
- Entering water temperature 70°C
- Max speed
UNIT SCOPE
The air conditioners from the integrated
system of the FW-R series are autono-
mous units designed and manufactured to
maintain the best ambient conditions.
With sombre and elegant lines, they are
particularly quiet that makes them suit-
able to be installed in domestic or com-
mercial ambients.
They are supplied with a water cooled con-
densing unit and besides carrying out the
typical functions of cooling, dehumidi-
fication, ventilation and filtration of the
air, present notable advantages from the
point of view of installation and applica-
tion.
They permit the heating in winter when
equipped with the heating coil (water or
electric); they achieve an efficient zone
division of the spaces by the independent
operation of each unit; they ensure an
economy of service by the rapid control
of the ambient conditions by virtue of the
reduced system thermal inertia; and they
operate silently because of the thermo-
acoustic insulation of the compressor.
All the units are completely factory assem-
bled and individually tested
With the FW-R air conditioner the
architectural, aesthetic and acoustic
problems associated with traditional
external air cooled heat exchangers and
fans are resolved.
FW-R must be installed internally, requires
connection to a water network and has
limited water consumption.
The unit contains the entire refrigerant charge
of R410A
MODELS AVAILABLE
The air conditioners of the FW-R series are available in two sizes, in the version with refrigerant R410A:
- FW130R
- FW160R