23
FWR 1406 - 5388000_02
0
100
200
300
400
500
23.5 bar
29 bar
0
100
200
300
400
15 20 25 30
FW130R
[l/h]
23.5 bar
29 bar
[l/h]
[°C]
FW160R
15 20 25 30
[°C]
WATER CONSUMPTION
Entering water temperature [°C]
Entering water temperature [°C]
Water consumption [l/h] Water consumption [l/h]
Model
Sound power level expressed in dB
Sound pressure
level
Speed
Central band frequency [Hz] Overall
125 250 500 1000 2000 4000 8000 dB dB[A] dB[A]
FW130R
Maximum 41,9 51,2 42,8 39,3 33,1 30,3 23,9 62,1 52,5 44,0
FW160R
Maximum 45,4 54,7 46,3 42,8 36,6 33,8 27,4 65,6 56,0 47,5
SOUND POWER LEVEL AND SOUND PRESSURE LEVEL
Level of sound pressure (A-weighted) measured in an 85 m
3