EN - 9NLC_A COD: 1606.4037360_00
9. ELECTRICAL DATA TABLE
L1 L2 L3
PHASE
EARTH (PE)
Model
Vers.*
Power
No.
Compressors
No. Fans
Total absorpon Recommended cable sec. for Lmax = 50 m / 1 968,50 Inch
LRA MCA MOP
Fuse
(recommended
No. Phases
No. cables
per phase
Sec. Phase Sec. PE IL
[A] [A] [A] [A] [mm²] [mm²] [A]
NLC0750 A 575/3/60 4 6 223,7 121,6 145,3 125 3 1 50 25 200