AERMEC NRP 0800 - POWER SUPPLY 575 V; Peak current (LRA); POWER SUPPLY 208 V

AERMEC NRP 0800
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22.11  5806712_07 39
POWER SUPPLY 575V
Version
Integrated
hydronic kit user
side
Integrated
hydronic kit,
recovery side
0800 0900 1000 1250 1400 1500 1650 1800
Peak current (LRA)
A 00 00 A 221 271 284 360 371 390 402 423
A 00 R1/R2 A 225 278 291 367 381 400 412 433
A 00 R3/R4 A 226 281 294 370 385 404 416 437
A P1/P2 00 A 225 275 288 367 378 397 409 430
A P1/P2 R1/R2 A 230 283 296 374 388 407 419 440
A P1/P2 R3/R4 A 231 285 298 377 392 411 423 444
A P3/P4 00 A 226 276 289 370 381 400 412 433
A P3/P4 R1/R2 A 231 284 297 377 391 410 422 443
A P3/P4 R3/R4 A 232 286 299 380 395 414 426 447
Minimum circuit
amperage (MCA)
A 00 00 A 122 124 133 176 209 238 244 246
A 00 R1/R2 A 126 131 140 183 219 248 254 256
A 00 R3/R4 A 127 134 143 186 223 252 258 260
A P1/P2 00 A 126 128 137 183 216 245 251 253
A P1/P2 R1/R2 A 131 136 145 190 226 255 261 263
A P1/P2 R3/R4 A 132 138 147 193 230 259 265 267
A P3/P4 00 A 127 129 138 186 219 248 254 256
A P3/P4 R1/R2 A 132 137 146 193 229 258 264 266
A P3/P4 R3/R4 A 133 139 148 196 233 262 268 270
Maximum over
-
current permitted
by the protection
device (MOP)
A 00 00 A 146 149 158 211 258 288 293 280
A 00 R1/R2 A 150 156 165 218 268 298 303 290
A 00 R3/R4 A 151 159 168 221 272 302 307 294
A P1/P2 00 A 150 153 162 218 265 295 300 287
A P1/P2 R1/R2 A 155 161 170 225 275 305 310 297
A P1/P2 R3/R4 A 156 163 172 228 279 309 314 301
A P3/P4 00 A 151 154 163 221 268 298 303 290
A P3/P4 R1/R2 A 156 162 171 228 278 308 313 300
A P3/P4 R3/R4 A 157 164 173 231 282 312 317 304
POWER SUPPLY 208V
Version
Integrated
hydronic kit user
side
Integrated
hydronic kit,
recovery side
0800 0900 1000 1250 1400 1500 1650 1800
Peak current (LRA)
A 00 00 A 611 784 820 979 1004 1065 1103 1178
A 00 R1/R2 A 622 803 839 998 1030 1091 1129 1204
A 00 R3/R4 A 625 810 846 1005 1041 1102 1140 1215
A P1/P2 00 A 622 795 831 998 1023 1084 1122 1197
A P1/P2 R1/R2 A 634 814 850 1016 1049 1110 1148 1223
A P1/P2 R3/R4 A 636 821 857 1024 1060 1121 1159 1234
A P3/P4 00 A 625 798 834 1005 1030 1091 1129 1204
A P3/P4 R1/R2 A 636 817 853 1024 1056 1117 1155 1230
A P3/P4 R3/R4 A 639 824 860 1031 1067 1128 1166 1241
Minimum circuit
amperage (MCA)
A 00 00 A 294 335 390 438 493 542 578 609
A 00 R1/R2 A 305 354 409 457 519 568 604 635
A 00 R3/R4 A 308 361 416 464 530 579 615 646
A P1/P2 00 A 305 346 401 457 512 561 597 628
A P1/P2 R1/R2 A 317 365 420 475 538 587 623 654
A P1/P2 R3/R4 A 319 372 427 483 549 598 634 665
A P3/P4 00 A 308 349 404 464 519 568 604 635
A P3/P4 R1/R2 A 319 368 423 483 545 594 630 661
A P3/P4 R3/R4 A 322 375 430 490 556 605 641 672
Maximum over
-
current permitted
by the protection
device (MOP)
A 00 00 A 350 409 464 524 603 651 688 694
A 00 R1/R2 A 361 428 483 543 629 677 714 720
A 00 R3/R4 A 364 435 490 550 640 688 725 731
A P1/P2 00 A 361 420 475 543 622 670 707 713
A P1/P2 R1/R2 A 373 439 494 561 648 696 733 739
A P1/P2 R3/R4 A 375 446 501 569 659 707 744 750
A P3/P4 00 A 364 423 478 550 629 677 714 720
A P3/P4 R1/R2 A 375 442 497 569 655 703 740 746
A P3/P4 R3/R4 A 378 449 504 576 666 714 751 757