22.11  5806712_07 9
OPERATING RANGE
In their standard conguration, the units are not suitable for installation in salty environments.
The values indicated in the table refer to the min. and max. limits of the unit, valid for T = -22.0 °F (cooling mode) and ∆T = -22.9 °F (heating mode).
If the unit is installed in particularly windy locations the provision of wind barriers may be necessary to avoid malfunctions. It should be installed if wind speed is above 4.3 knot.
WARNING: Under no circumstances does the unit have to be operated outside the operating limit under penalty of the warranty expiration. Aermec S.p.A.
cannot be held responsible for any malfunction of the units which are operated outside the established limits and for their consequences.
OPERATING COOLING MODE RANGE
Key
A Outdoor air temperature (°F)
B Water produced (°F)
1 Standard mode
B
1
A
0
14
20
40
60
80
100
120
114.8
140
°F
30 40
39.2
44.6 64.450 60 70
104
°F
OPERATING HEATING MODE RANGE
Key
A Outdoor air temperature - dry
bulb (°F)
B Water produced (°F)
1 Standard mode
60
70
80
77
90
100
104
110
120
130
131
140
°F
-20
5
0
23
4020 60 80
107.6
120100
°F