26
N
Air / water units type 00
Cold only
Air / water units other versions
Free-cooling, Total recovery, Heat pump
Notes
C1 Circulation pump Circulation pump -
C2 Antifreeze heating element Antifreeze heating element -
C3 Liquid solenoid Liquid solenoid -
C4 Compressor line contactor Compressor line contactor -
C5 Compressor star contactor Compressor star contactor -
C6 Compressor triangle contactor Compressor triangle contactor -
C7 Liquid Inj./econ./oil cooler Liquid Inj./econ./oil cooler -
C8 General alarm General alarm -
C9
Step capacity control:
- Compressor capacity control 1:
Modulating capacity control:
- Power decrease valve
Step capacity control:
- Compressor capacity control 1:
Modulating capacity control:
- Power decrease valve
CP Power 75%
C10
Step capacity control:
- Compressor capacity control 2:
Modulating capacity control:
- Power increase valve
Step capacity control:
- Compressor capacity control 2:
Modulating capacity control:
- Power increase valve
CP Power 40%
C11
Step capacity control:
- Compressor capacity control 3:
Daikin Modulating capacity control:
- Minimum power valve
Bitzer Modulating capacity control:
-Economizer
Step capacity control:
- Compressor capacity control 3:
Daikin Modulating capacity control:
- Minimum power valve
Bitzer Modulating capacity control:
-Economizer
CP Power
25% (5 step) or
12% (4 step)
C12
5 Step capacity control:
- Compressor capacity control 4:
4 Step capacity control:
- Liquid injection electrovalve 2
5 Step capacity control:
- Compressor capacity control 4:
4 Step capacity control:
- Liquid injection electrovalve 2
Power CP 12% or
Liquid Inj./econ./oil
cooler
C13 Fan motor 1 Fan motor 1 -
C14 - Cycle inverter valve (VIC) -
C15 - Pressure switch bypass solenoid valve (VSBP) -
C16 - 3-way recovery valve -
C17 - VR recovery -
C18 - VB recovery -
C1 EXP - Glycolated water pump (Glycol free) -
C2 EXP - Antifreeze heating element glycol side (Glycol free) -
C3 EXP - Not used -
C4 EXP - Not used -
N Air / water units type 00 / 01 Water / water units type 03 / 04 NOTES
Y1 Condenser fan motor speed regulation Inverter pump / modulating valve speed regulation -
Y2 - -
Y3 0-10 volt output, water outlet 0-10 volt output, water outlet -
Y4 0-10 volt output, water inlet 0-10 volt output, water inlet -
Y5 ---
Y6 ---
ANALOGUE OUTPUTS
DIGITAL OUTPUTS
NS-NSH UNITS