Maintenance&Trouble Shooting
31
Type of Fault
Code
Name Description Recommend Solution
J05 ParallelComWarning
Communication between
master inverter and slaver
ones abnormal in parallel
mode.
Check whether the parallel
communication line is damaged, the
terminal is loose, the wiring hole position
is correct, and make corrections.
• Power off, then restart.
If fault still occurs continuously and
frequently, please ask help for local
distributors.
J04 GndAbnormalWarning
Poor grounding or no
grounding wire has been
detected.
Check whether the ground wire of the
inverter is properly connected and
whether the ground impedance is over,
and make corrections.
• Power off, then restart.
If fault still occurs continuously and
frequently, please ask help for local
distributors.