2.Safety & Symbols
2.1 Safety Precautions
1. All work on the inverter must be carried out by qualified electricians.
2. The device may only be operated with PV panels.
3. The PV panels and inverter must be connected to the ground.
4. Do not touch the inverter cover until 5 minutes after disconnecting both DC
and AC power supply.
Safety & Symbols
03
Type Max AC Current (A) Rated current of AC breaker (A)
Circuit Breaker Recommendation
Note:
The Inverter can be only connected to low-voltage grid.
(230/400Vac, 50/60Hz).
Surge Protector Recommendation
• AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 2.5KV.
• DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 3.2KV.
BNT030KTL
BNT036KTL
BNT040KTL
BNT050KTL
BNT060KTL
48
60
65
80
96
63
100
100
100
125