Why does my Air Techniques AS10 motor try to start and then the circuit breaker trips?
- BBrad GriffinAug 10, 2025
If your Air Techniques Air Compressor motor tries to start but the circuit breaker trips, it could be due to several reasons. The voltage might be too low; AS10 and AS21 models need a minimum of 108 Volts, while AS12, AS22, AS30, AS50, AS70, and AS100 models require at least 198 Volts. If the voltage is insufficient, a boost transformer installation might be required. Also, the power supply cable could be too small; refer to the SITE REQUIREMENTS Table for appropriate sizing. If neither of these resolves the issue, further assistance is needed.