4. Operation
4-8
A070368-1
SG0114-1
Install a switch between the output terminal and
the load to switch“ON/OFF” the load. Do not
switch the load on/off directly by the
circuit-breaker of the machine.
It could cause damage to the Connect the
connecting cable to the load so that the output
terminals should not touch each other.
circuit-breaker.
4.4.1 How to connect three phase load
In case of three-phase load:
Each electric current value of each phase (U・V・W) should not
exceed the values in the following table. But please note that
the data in the table is based on power factor of 80% (in case
of electric motor operated). In case of different power factor,
take care not to be overloaded, and reduce load.
Type Permissible current value
50Hz/200V 107A
60Hz/220V 118A
50Hz/380V 56.2A
50Hz/400V 53.4A
60Hz/440V 59.0A
In case inverter load:
The inverter capacity (input kVA of inverter) should not exceed the following value (within rated
output ÷ 3.0). Also select generator so that the rated output (kVA) of generator so that the rated
output (kVA) of generator may be three times of the inverter capacity.
Example: In case of SDG45S,at 50Hz, 37kVA ÷3.0 = 12.3kVA.
50Hz: 12.3kVA (Input kVA of inverter) It is possible to use inverter capacity up to this value.
60Hz: 15.0kVA (Input kVA of inverter) It is possible to use inverter capacity up to this value.
Switch panel for
switching on/off load
Load