11-7
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
11.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST TrendHST
Decreasing No Change Increasing
HST SC SC SC>90
85<HST90D1D2D2
82 < HST 85 SR D1 D2
80 < HST 82 SR SR D1
78 < HST 80 Norm Norm SR
HST 78 Normal
11.7.6 Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT OAT 8 AND TLD<>DI
Case 2: OCT OAT 12 AND TLD 30 minutes.<>
Case 3: OCT is Invalid AND TLD DI>
Case 4: Unit is ust switched to STBY AND OCTj<OAT-8
Case 5: NLOAD 0 AND OCT OAT -8=<
OCT Outdoor Coil Temperature
OAT Outdoor Air Temperature
TLD Time from Last Deicing
DI Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be
increased. If deicing time is longer then former deicing time, the deicing interval time will be
decreased.
(NA for GC 9 and GC 12 DCI)
CONTENTS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell GC 18 DCI and is the answer not in the manual?

Airwell GC 18 DCI Specifications

General IconGeneral
BrandAirwell
ModelGC 18 DCI
CategoryHeat Pump
LanguageEnglish

Related product manuals