Page 55
English
Technical data
CLH STD 182 202 242 302 352
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power kW 18.8 25.4 31.0 36.0 42.1
Rated current A 22.2 30.6 41.9 51.4 51.3
Max. current (FLA) A 32.1 43.3 49.9 60.8 71.6
Max. start-up current (LRA) A 116 150 176 207 256
External fuses (A) 50 63 63 80 100
Max. cable section (1) mm
2
16 25 25 35 35
CLH STD with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power kW 19.6 26.2 32.5 37.5 43.9
Rated current A 24.3 32.7 45.7 55.2 56.2
Max. current (FLA) A 34.2 45.4 53.7 64.6 76.5
Max. start-up current (LRA) A 118 152 180 211 260
External fuses (A) 50 63 63 80 100
Max. cable section (2) mm
2
16 25 25 35 35
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
(2) Data which refer to a single pump.
CLH STD 402 502 552 602
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power kW 49.9 57.6 64.7 71.8
Rated current A 56.2 66.4 81.3 91.2
Max. current (FLA) A 84.8 97.8 108.8 119.8
Max. start-up current (LRA) A 269 322 370 381
External fuses (A) 100 125 125 160
Max. cable section (1) mm
2
35 50 70 70
CLH STD with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power kW 51.7 59.4 66.5 73.6
Rated current A 61.1 71.3 86.2 96.1
Max. current (FLA) A 89.7 102.7 113.7 124.7
Max. start-up current (LRA) A 274 327 375 386
External fuses (A) 100 125 125 160
Max. cable section (2) mm
2
35 50 70 70
Unit Electrical data