1652H311 Ed.03
12
Keypad
Indicators
Pressing it for 3 seconds activates/deactivates Stand-By mode. In this mode, regulation is paused and the
m icon is displayed.
In the programming menu, this exits the parameter without saving changes, returns to previous level or
exits programming.
Pressing once displays the temperature of probe S2 for 2 seconds (If it is enabled).
Pressing it for 3 seconds starts/stops the defrost.
In the programming menu, this allows scrolling around the different levels, or, during the setting of a
parameter, changing its value.
Pressing it for 3 seconds activates/deactivates continuous cycle mode.
In the programming menu, this allows scrolling around the different levels, or, during the setting of a
parameter, changing its value.
Pressing once activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu.
Pressing it for 6 seconds accesses the expanded programming menu.
In the programming menu, this accesses the level shown on the display or, during the setting of a
parameter, accepts the new value.
Pressing once displays the current effective value of the Set Point, taking into consideration temporary
modifications by other parameters (C10 ó C12).
When an alarm is underway, pressing once mutes the acoustic alarm.
Pressing for 3 seconds accesses the Set Point setting.
Fixed: Stand-By Mode activated. Regulation is
paused.
Flashing: Controlled shutdown process for the
regulation underway.
Fixed: Cold room door open.
Flashing: The door has been open for a greater
time than has been defined in parameter A12.
There is an active alarm, but not an active HACCP
alarm.
Fixed: HACCP alarm active.
Flashing: HACCP alarm registered and
unconfirmed. Press the key to confirm an MUT
HACCP alarm.
Fixed: Evaporator fans active.
Flashing: The evaporator fans should be active
but a delay is preventing this.
Fixed: The cold solenoid is active.
Flashing: The solenoid should be active but a
delay or protection is preventing this.
Fixed: Compressor active.
Flashing: The compressor should be active but a
delay or protection is preventing this.
Defrost relay active.
Continuous cycle mode active.
Cold room light active.
Alarm underway muted.
Temperature displayed in ° Fahrenheit /
° Centigrade.
Programming mode active.
Fixed: CAMM module in operation.
Flashing: Malfunction in CAMM module.
Bluetooth activated (CAMM module only).