Alarm delay
These delays prevent the display of specific alarms while allowing the unit to recover normal operation after certain
events.
• Delays in start-up (A08): Delays the activation of the alarms upon receiving power supply (start-up or after a
fault in the power supply). This allows starting up the installation avoiding constant alarm statuses.
• Alarm delay (A07): It delays the activation of the high and low pressure alarms (A03 and A05) from the time
that the programmed values are reached.
• Turn-on delay time of alarms due to digital input 5 (I09): It delays the activation of activated alarms due to
digital input 5. The type of alarm to be activated depends on the configuration of parameter I07. It does not
take effect if parameter I07 is set to 2 (Thermal alarm).
• Turn-on delay time of alarms due to digital input 6 (I10): It delays the activation of activated alarms due to
digital input 6. The type of alarm to be activated depends on the configuration of parameter I08. It does not
take effect if parameter I08 is set to 2 (Thermal alarm).
Remote disconnection
This function allows stopping / starting regulation with an external signal via the digital input 5 or 6.
The digital input 5 or 6 must be configured as a remote disconnection (I07 or I08=5).
When stopping or starting regulation, the compressors / stages and fans will stop or start in accordance with the
timings set in parameters t01 to t08.
Connectivity
The AKO-D14545-C model has a port for RS485 (MODBUS) data connection, which enables remote management via
the AKO XaviP Edge gateway and the akonet.cloud platform.
A different address must be assigned to each unit on the same network. This address is defined by parameter b20.
LAN
12
13 14
AKO-D14545-C
ESC
?
SET
AKOCAM
GND
Tr+
Tr-