10. Fault messages
If an error occurs in the system, the display will show the reason.
This is only displayed when the panel is on standby.
Battery too low (Battery low): If the vehicle, boat or building has a
battery voltage of less than 10.5V, the boiler stops. It is automatically
reset when the voltage reaches 11V.
Fan failure: Faulty fan speed. In order to reset, disconnect 12V from
the boiler and reconnect (automatic reset after 5 minutes).
Gas failure: Gas nished. Reset by switching off and restarting the
boiler in accordance with item 1.
Overheat red fail (Overheat 1): Overheating protection (red cable)
triggered. To reset, disconnect 12V from the boiler and reconnect.
Overheat blue fail (Overheat): Overheating protection (blue cable)
triggered. To reset, disconnect 12V from the boiler and reconnect.
Window open (Window switch act): Window open, the boiler stops
for gas. Gas operation in the boiler starts again when the window is
closed. The electrical operation remains in function. Check the vehicle,
boat or building manual to see whether this function is installed.
Connection failure (Serial bus failure): There is a connection fault
between boiler and panel. To reset, disconnect 12V from the boiler
and reconnect.
Panel failure 1 (Cristal 32K fail): Panel fault.
Panel failure 2 (Watch 32K fail): Panel fault.
Text in brackets ( ) refers to earlier program editions.
11. Emergency start
• Disconnect the 12V cable and the cable to the panel on the boiler.
• Connect a cable between 2 and 9 in the connector on the boiler.
• Reconnect 12V to the boiler
Now the boiler starts with gas and 1kW. Adjustment of the room
temperature is not working. Constant pump operation is set.