142 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
Table 51 - Input Data – 1791ES-IB16 Modules
Instance Hex
(decimal)
Connection
Type
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
205 (517) Safety and
standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
225 (549) Safety and
standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
300 (768) Only standard 0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Input Power
Error
315 (789) Safety and
standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
2 Combined
Safety In
Status
Reserved Input Power
Error
(1)
Reserved Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
335 (821) Safety and
standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4 Reserved Reserved Input Power
Error
(1)
Reserved Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
365 (869) Safety and
standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9 Safety Input 8
2Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4 Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
5 Test Output 15
Status
Test Output 14
Status
Test Output 13
Status
Test Output 12
Status
Test Output 11
Status
Test Output 10
Status
Test Output 9
Status
Test Output 8
Status
6 Reserved Reserved Input Power
Error
(1)
Output Power
Error
(1)
Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
385 (901) Only standard 0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Input Power
Error
1 Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
2 Test Output 15
Status
Test Output 14
Status
Test Output 13
Status
Test Output 12
Status
Test Output 11
Status
Test Output 10
Status
Test Output 9
Status
Test Output 8
Status
(1) This data is only diagnostic data. This data does not have safety integrity.