86 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Chapter 5 Configure the I/O Modules
Configure the Safety 
Connections
Follow these steps to complete entries when you choose the Safety tab.
1. From the Module Properties dialog box, choose the Safety tab to see the 
Safety dialog box.
2. Click Advanced to configure Requested Packet Interval (RPI) and 
Configure Connection Reaction Time Limit (CRTL).
Make sure that input RPI is set to match the need. The smallest input 
RPI allowed is 6 ms. Small RPIs consume network bandwidth and can 
cause nuisance trips because other devices cannot get access to the 
network.
As an example, a safety input module with only E-stop switches 
connected to it generally can work well with settings of 50…100 ms. An 
input module with a light curtain guarding a hazard can need the fastest 
response that is possible.
We suggest that you keep the 
Timeout Multiplier and Network 
Delay Multiplier at their default 
values of 2 and 200.
See the GuardLogix Controllers User 
Manual, which is listed in the 
Additional Resources on page 10
, for 
more information about the CRTL.