Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Calibrate Your Analog Modules 137
12. Enter the value shown on the DVM onto your dialogs (10.0057 in this
example).
13. Repeat these steps for the other channel.
14. From the Device Parameters dialog, select All, and click Finish Calibration
to complete the calibration process.
You see the EDS Editor dialog that prompts you to download to the
module.
15. From the EDS Editor dialog, click Yes.
Type in the
resulting value
from your
DVM.