4–18 Scanner Configuration and Programming
Publication
17476.6 - July 1996
Example of Remote Output Reset Control
By default the scanner sets the bits in M0:e.24 through M0:e.27 to 1
wherever there are configured devices present. This commands all
devices’ outputs to reset regardless of their Hold Last State switch.
The application program can remove commanded reset of devices by
resetting bits to 0.
1001xxxxxxxxxxxx
1000xxxxxxxxxxxx
0100xxxxxxxxxxxx
0100xxxxxxxxxxxx
0123456789101112131415
M0 File
M0:e.24
M0:e.25
M0:e.26
M0:e.27
1 100100001000100
Device Address, Word 1
G
File
RIO Rack 0
Starting Group
0246
RIO Rack 1
Starting Group
0246
RIO Rack 2
Starting Group
0246
RIO Rack 3
Starting Group
0246
M0
(Control) File
Bit Number (decimal)
Logical Rack 0 Remote Output Reset Word 24
Logical Rack 1 Remote Output Reset Word 25
Logical Rack 2 Remote Output Reset Word 26
Logical Rack 3 Remote Output Reset Word 27
e = slot number of the SLC rack containing the scanner
x = not used/defined