5–17RIO Block Transfer
Publication
17476.6 - July 1996
M0 Control Information
M1 Status Information
EN
Block T
ransfer Failure After Startup of T
ransmission Across RIO Link
DN
ER
TO
Status Flag
Control
Flag
EW
ST
Block T
ransfer Failure after Startup of Transmission Across the RIO
Link
This example illustrates control and status changes when a BT fails
after it starts.
The SLC control program fills in the M0 BT output/control buffer
and sets the EN flag.
The scanner detects the EN flag, validates the M0 information,
puts the BT request on the RIO link successfully, and sets the EW
and ST flags in the M1 BT input status buffer.
The scanner receives a BT reply (with some error) from the RIO
link device, fills in the M1 BT buffer’s error code field, and sets
the ER flag.
The SLC control program detects the ER flag, examines the M1
BT buffer error code, and clears the EN flag after processing the
error.
The scanner detects that the SLC control program has processed
the reply in the M1 BT buffer and clears the EW, ST and ER
flags.