Appendix A Analog I/O Module Tag Definitions
Ch[x].LowSignal REAL Signal value that lets you scale signal units (V, mA) into
Engineering Units.
Corresponds to the C.Ch[x].LowEngineering tag. That is,
this tag’s value is scaled to the lowest Engineering Unit.
For more information on how Signal values correspond to
Engineering values, see page 32
Any value that is less than the
C.Ch[x].HighSignal tag value.
Current input type: 4.0 mA =
default
Voltage input type: -10.0V=
default
Ch[x].HighSignal REAL Signal scaling value that lets you scale signal units (V, mA)
into Engineering Units.
Corresponds to the C.Ch[x].HighEngineering tag. That is,
this tag’s value is scaled to the highest Engineering Unit.
For more information on how Signal values correspond to
Engineering values, see page 32
Any value that is greater than the
C.Ch[x].LowSignal tag value
Current input type: 20.0 mA =
default
Voltage input type: 10.0V=
default
Ch[x].LowEngineering REAL Low engineering scaling point
Corresponds to the C.Ch[x].LowSignal tag value.
For more information on how Signal values correspond to
Engineering values, see page 32
0.0 = default
(In voltage applications, default =
C.Ch[x].LowSignal tag value)
Ch[x].HighEngineering REAL High engineering scaling point
Corresponds to the C.Ch[x].HighSignal tag value.
For more information on how Signal values correspond to
Engineering values, see page 32
100.0 = default
(In voltage applications, default =
C.Ch[x].HighSignal tag value)
Ch[x].LLAlarmLimit REAL Low Low Process Alarm limit
Triggers the I.Ch[x].LLAlarm tag when the I.Ch[x].Data tag
value is less than this tag’s value.
0.0 = default
Ch[x].LAlarmLimit REAL Low Process Alarm limit
Triggers the I.Ch[x].LAlarm tag when the I.Ch[x].Data tag
value is less than this tag’s value
0.0 = default
Ch[x].HAlarmLimit REAL High Process Alarm Limit
Triggers the I.Ch[x].HAlarm tag when the I.Ch[x].Data tag
value is greater than this tag’s value.
100.0 = default
Ch[x].HHAlarmLimit REAL High High Process Alarm Limit
Triggers the I.Ch[x].HHAlarm tag when the I.Ch[x].Data
tag value is greater than this tag’s value.
100.0 = default
Ch[x].AlarmDeadband REAL Deadband that keeps Process Alarms triggered as long as
the I.Ch[x].Data tag value remains within the deadband of
the Process Alarms value
Any non-negative value
0.0 = default
Table 28 - 1756-IF8I Module - Configuration Tags (continued)
Tag Name Data Type Definition Valid Values

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-IT16 and is the answer not in the manual?

Allen-Bradley 1756-IT16 Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-IT16
CategoryI/O Systems
LanguageEnglish

Related product manuals