Rockwell Automation Publication 1756-UM058G-EN-P - November 2012 217
Use Ladder Logic To Perform RunTime Services and Reconfiguration Appendix C
Enter Message Configuration
After creating a tag, you must enter certain parameters for the message 
configuration. This information is entered on the Configuration and 
Communication tabs of the Message Configuration dialog box.
The Message Configuration dialog box is accessed by clicking the box with the 
ellipses (in the Message Control field).
In RSLogix 5000 software, version 10.07.00 or later, the Message Configuration 
dialog boxes changed significantly to make it easier for you to configure your 
messages.
• For example, in version 9.00.00 or earlier, depending on the Message Type, 
you are required to configure some combination of the following:
-Service Code
-Object Type
-Object ID
-Object Attribute
-Source
-Number of Elements
-Destination
• In version 10.07.00 or later, after you choose a Service Type, RSLogix 5000 
software fills in most of the fields listed above. The fields you must fill in are 
dependent on what Service Type you choose. For example, with the Reset 
Electronic Fuse service, you must know only the Source Element and the 
Destination.
The following section shows how to configure messages with RSLogix 5000 
software, version 10.07.00 or later. A table describes the relationship of the 
fields in both dialog boxes so you can configure messages by using 
RSLogix 5000 software version 9.00.00 or earlier.