120 Rockwell Automation Publication 1756-UM535D-EN-P - November 2012
Chapter 6 Configure the Redundancy Modules
Event Log Tab
The Event Log tab provides a history of events that have occurred on the
redundant chassis.
These system events are indicated in the event logs:
• Qualification stages entered and completed
• Module insertion/removal
• Firmware errors
• Communication events and errors
• Configuration changes
• Other system events that affect qualification and synchronization
The Event Log tab can be customized to view the log specific to only one chassis
or the event logs of both redundant chassis. You can alter your view of the event
logs by changing the Auto-Update and Partner Log parameters.
Figure 29 - Settings for Event Log Views
IMPORTANT
The events logged in this tab are not always indicative of an error. Many of
the events logged are informational only.
To determine if additional action or troubleshooting is required in response
to an event, see the Event Classifications
table on page 121.
Table 20 - Settings for Event Log Views
Use this setting To
Auto-Update Keep the log from updating while you’re viewing it.
Partner Log View only the event log for the module you are accessing.
Check On to keep the log updating automatically. Check Close to view only the log of one redundancy module.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-RM and is the answer not in the manual?

Allen-Bradley 1756-RM Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-RM
CategoryControl Systems
LanguageEnglish

Related product manuals