Publication 1794-6.5.12 - November 1997
4-2 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Sensor Types Individual input channels are configurable to operate with the following
sensor types:
You select individual channel ranges using write word 1 of the block
transfer write instruction.
RTD Type
Sensor type for channels 0 through 3
Sensor type for channels 4 through 7
Resistance (default)
100 ohm Pt a = 0.00385 Euro (–200 to +870°C)
200 ohm Pt a = 0.00385 Euro (–200 to +400°C)
100 ohm Pt a = 0.003916 U.S. (–200 to +630°C)
200 ohm Pt a = 0.003916 U.S. (–200 to +400°C)
100 ohm Nickel a = 0.00618 (–60 to +250°C)
200 ohm Nickel a = 0.00618 (–60 to +200°C)
120 ohm Nickel a = 0.00672 (–80 to +320°C)
10 ohm Copper a = 0.00427 (–200 to +260°C)
Thermocouple Type
Sensor type for channels 0 through 3
Sensor type for channels 4 through 7
mV (default)
B 300 to 1800°C (572 to 3272°F)
E –270 to 1000°C (–454 to 1832°F)
J –210 to 1200°C (–346 to 2192°F)
K –270 to 1372°C (–454 to 2502°F)
L –200 to 800°C (–328 to 1472°F)
N –270 to 1300°C (–450 to 2372°F)
R –50 to 1768°C (–58 to 3214°F)
S –50 to 1768°C (–58 to 3214°F)
T –270 to 400°C (–454 to 752°F)
Allen-Bradley PLCs