2–2
How to Install Your Thermocouple/mV Input Module
Publication
1794-6.5.7
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC
Low Voltage, by applying the safety requirements of EN 61131–2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
Guidelines for Handling Lithium Batteries, publication AG-5.4
Automation Systems Catalog, publication B111
The wiring of the terminal base unit is determined by the current
draw through the terminal base. Make certain that the current draw
does not exceed 10A.
!
ATTENTION: Total current draw through the
terminal base unit is limited to 10A. Separate power
connections may be necessary.
!
ATTENTION: Do not daisy chain power or ground
from the thermocouple terminal base unit to any ac or
dc discrete module terminal base unit.