Threshold for controller to declare a `Hardware Preservation 
Fault’, and reset the module and disable power.
In the disabled power condition, only the OK status indicator is 
illuminated, and it is red. The module does not apply power 
until it has cooled below the Hardware Preservation Hysteresis 
limit. The module then enters fault mode, records the fault in 
the major fault log, and displays `CPU Temperature Fault’ on 
the front panel.
Threshold for controller to declare a `CPU Temperature Fault’ 
major recoverable fault. If a fault handler does not clear the 
fault, then the module enters fault mode, records the fault in 
the major fault log, and displays `T17:C34 CPU Temperature 
Fault’ on the front panel.
Threshold for controller to declare a `T17:C35 Controller internal 
temperature is approaching operating limit’ minor fault and set 
the Diagnostics minor fault bit. 
The fault is recorded in the minor fault log, but is not displayed 
on the front panel. If the temperature returns to an acceptable 
range, the Diagnostics minor fault bit clears, but the minor fault 
record remains. 
 Power to the 
controller is 
disabled 
Hardware Preservation 
Hysteresis Limit
Power does not 
become enabled 
when in this range
All power to the controller is disabled except 
to run the red OK status indicator and 
monitor the temperature.