Produce and Consume a Tag
38 Rockwell Automation Publication 1756-PM011J-EN-P - February 2018
• Verify that all multicast consumed tags of a produce tag are
configured with the same RPI. If they are not, some consumers will
fail to connect.
• For multicast consumers running Logix Designer releases v18 and
later, take one of these steps:
• Verify that all multicast consumed tags of a produce tag are
configured with the same RPI, or
• Verify that all multicast consumers are configured to Allow
Consumed Tags To Use RPI Provided By Producer.