60 Rockwell Automation Publication 2080-UM005B-EN-E - March 2015
Chapter 5 Communication Connections
4. Under Ethernet, click Port Settings.
5. Set Port State as Enabled or Disabled.
6. To manually set connection speed and duplexity, uncheck the option box
Auto-Negotiate speed and duplexity. Then, set Speed (10 or 100 Mbps)
and Duplexity (Half or Full) values.
7. Click Save Settings to Controller if you would like to save the settings to
your controller.
8. On the device configuration tree, under Ethernet, click Port Diagnostics to
monitor Interface and Media counters. The counters are available and
updated when the controller is in Debug mode.
Ethernet Host Name
Micro800 controllers implement unique host names for each controller, to be
used to identify the controller on the network. The default host name is
comprised of two parts: product type and MAC address, separated by a hyphen.
For example: 2080LC20-xxxxxxxxxxxx, where xxxxxxxxxxxx is the MAC
address.
The user can change the host name using the CIP Service Set Attribute Single
when the controller is in Program/Remote Program mode.
OPC Support Using RSLinx
Enterprise
Support for Open Platform Communications (OPC) using CIP symbolic has
been added from firmware release 7.0 onwards. This can be used in place of
Modbus addressing.
RSLinx Enterprise version 5.70 (CPR9 SR7) or later and FactoryTalk Gateway
version 3.70 (CPR9 SPR7) or later are required.