Programming Reference
B–15
Fault Classification
User
Address
Error
Code
(Hex)
Powerup Errors Non-User
Non-
Recoverable
Recoverable
S:6 0001
The default program was
loaded.
X
0002 Unexpected reset occurred.
X
0003 EEPROM memory is corrupt.
X
0008
A fatal internal programming
device error occurred.
X
0009
A fatal internal hardware
error occurred.
X
Fault Classification
User
Address
Error
Code
(Hex)
Going-to-Run (GTR) Errors
Non-User
Non-
Recoverable
Recoverable
S:6 0005 Retentive data is lost. X
0010
The downloaded program is
not a controller program.
X
0016
Startup protection after
power loss, S:1/9 is set. The
user must check for a
retentive data lost condition if
the user-fault routine was
executed with startup
protection.
X
Going-to-Run
errors occur when the controller is going from any mode to REM Run mode or from any
non-Run mode (PRG, SUS) to T
est mode.