6 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals
Publication 2711P-IN002G-EN-P - November 2009
USB Ports
The PanelView Plus and PanelView Plus Compact terminals contain a single, universal serial
bus (USB) port that comply with hazardous location environments. This section details the
field wiring compliance requirements and is provided in accordance with the National
Electrical Code, article 500.
400 and 600 Terminals Control Drawing
Selected nonincendive field wiring apparatus must have nonincendive circuit parameters
conforming with Table 2.
Table 1 - 400 and 600 USB Port Circuit Parameters
400 and 600
Terminals
V
oc
I
sc
C
a
L
a
Groups A and B Groups C and D Groups A and B Groups C and D
Series A and B 5.25V DC 1.68 A 10 µF 10 µF 15 µH 15 µH
Series C or
later
5.25V DC 1.68 A 10 µF 10 µF 3.5 µH 15 µH
Table 2 - Required Circuit Parameters for the USB Peripheral Device
V
max
V
oc
I
max
I
sc
C
i
+ C
cable
C
a
L
i
+ L
cable
L
a
USB
Peripheral
Device
Nonincendive Field
Wiring Apparatus
USB Port
Nonincendive Field Wiring
Associated Nonincendive Field Wiring Apparatus
PanelView Plus 400/600 Host Product

Other manuals for Allen-Bradley PanelView Plus 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PanelView Plus 600 and is the answer not in the manual?

Allen-Bradley PanelView Plus 600 Specifications

General IconGeneral
Resolution320 x 240 pixels
TouchscreenAnalog resistive
BacklightLED
Operating SystemWindows CE
Power Supply24V DC
Communication PortsEthernet, RS-232
Memory64 MB RAM
Operating Temperature0°C to 50°C
Enclosure RatingNEMA 4X
ProcessorXScale processor