POINT I/O EtherNet/IP Adapter 15
Publication 1734-IN590A-EN-P - March 2003
Environmental Conditions
Operational
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55°C (-4 to 131°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock): -40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat): 5 to 95% noncondensing
Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Operating 30g peak acceleration
Nonoperating 50g peak acceleration
Vibration IEC 60068-2-6 (Test Fc, Operating)
Tested 5g @ 10-500Hz
ESD Immunity IEC 61000-4-2:
4kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% pulse 100%AM from 900MHz
EFT/B Immunity IEC 61000-4-4:
+4kV at 2.5kHz on power ports
+2kV at 5.0kHz on signal ports
Surge Transient
Immunity
IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on signal
ports
+1kV line-line(DM) and +2kV line-earth(CM) on power
ports
Conducted RF
Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Emissions CISPR 11
Group 1, Class A
Enclosure Type Rating None (open-style)