110 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
Frame Voltage ND Rating Enclosure Frequency
(1)
(1) Consult the factory for further derate information at other frequencies.
Derate
5 460V 100 HP
• Open
• NEMA/UL Type1
• IP20
6…8 kHz
Frame Voltage
Class
ND/HD
Rating
(Amps)
Frequency
(kHz)
(1)
(1) Not all frequencies can be run on all drives.
Ambient Temp (C)
(2)
(2) Ambient Temp / Max. Surrounding Air Temperature is the air temperature surrounding the drive module. Rated ambient temperature is 40/40 C (ND/HD) for 400V class drives and 35/40 C (ND/HD) for 600V class drives.
Derate
9 400 300/245 PWM 50 35 20
1.5 256 335 354
2.0 245 325 341
4.0 207 258 295
6.0 175 223 256
8.0 150 193 225
10.0 128 170 200
600 208/170 PWM 50 35 20
1.5 194 223 249
2.0 180 208 233
4.0 83 104 124
6.0 60 78 94
8.0 47 62 74
10.0 39 51 62
15
20
25
30
35
40
45
50
40 50 60 70 80 90 100
% of Output FLA
8 kHz
6 kHz
Max. Surrounding Air Temp,
o
C
20
25
30
35
40
45
50
55
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
Iout (Amps)
Max. Surrounding Air Temperature °C
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
20
25
30
35
40
45
50
55
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C